This product complies with the national standards GB1094 "Power Transformers" and GB/T6451 "Technical Parameters and Requirements for Three phase Oil immersed Power Transformers". On load voltage regulation range: 10 ± 4 × 2.5% kV, 35 ± 3 × 2.5% kV, off excitation voltage regulation range: 10 ± 2 × 2.5% kV, 35 ± 2 × 2.5% kV. The voltage can be manually, electrically or automatically adjusted within the voltage regulation range on the primary side with the help of on load and off excitation voltage regulation switches to ensure the stability of the output voltage. The device body adopts three positioning points of upper, middle, and lower, as well as special anti loosening and shock-absorbing measures, which eliminates the need for core inspection before installation and has shock-absorbing function. The fuel tank is made of high-quality steel plate with high mechanical strength. The rubber strips and pads are made of the latest high-quality acrylic products, which will not age after long-term operation and effectively prevent transformer oil leakage.
Oil free, with strong fire resistance, eliminating the risk of oil leakage; Capable of withstanding short-circuit current and overvoltage, and adapting to harsh environments.
Using environmentally friendly materials, low noise and no pollution, to assist in the construction of a green power grid.
Efficient cooling system ensures that the equipment maintains low temperature during long-term operation, effectively extending the service life of the equipment.
Humanized design, simple operation, convenient and fast daily inspection and maintenance, significantly reducing operating costs.
Durable shell design, impact resistance, corrosion resistance, able to adapt to various complex and harsh working environments.
Modular structure design, supporting quick disassembly and assembly, combined with intelligent monitoring system, making operation and maintenance work more worry free and effortless.
35kV oil-immersed three-phase double-winding unexcited voltage regulating power transformer
Rated capacity (kVA) | Rated voltage and tapping range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | ||
| HV | Tap range(%) | LV | ||||||
| 3150 | 35~38.5 | ±2×2.5 ±5 | 3.15 | Yd11 | 0.36 | 7.0 | 1.7 | 20.7 |
| 4000 | 6.3 | 0.36 | 2 | 24.6 | ||||
| 5000 | 10.5 | 0.36 | 2.4 | 28.2 | ||||
| 6300 | 3.15 | 0.36 | 2.9 | 31.5 | ||||
| 8000 | ±2×2.5 | 3.3 | YNd11 | 0.28 | 8.0 | 4 | 34.6 | |
| 10000 | 6.3 | 0.28 | 4.8 | 40.8 | ||||
| 12500 | 6.6 | 0.24 | 5.5 | 48.4 | ||||
| 16000 | 10.5 | 0.24 | 6.7 | 59.2 | ||||
| 20000 | 10.5 | 0.24 | 7.9 | 71.6 | ||||
| 25000 | 10.5 | 0.2 | 10.0 | 9.4 | 84.6 | |||
| 31500 | 10.5 | 0.2 | 11.1 | 100.8 | ||||
35kV oil-immersed three-phase double-winding on-load regulating power transformer
Rated capacity (kVA) | Rated voltage and tapping range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | ||
HV | Tap range (%) | LV | ||||||
| 3150 | 35~38.5 | ±2×2.5 ±5 | 3.15 | Yd11 | 0.36 | 7.0 | 1.7 | 20.7 |
| 4000 | 6.3 | 0.36 | 2 | 24.6 | ||||
| 5000 | 10.5 | 0.36 | 2.4 | 28.2 | ||||
| 6300 | 3.15 | 0.36 | 2.9 | 31.5 | ||||
| 8000 | ±2×2.5 | 3.3 | YNd11 | 0.28 | 8.0 | 4 | 34.6 | |
| 10000 | 6.3 | 0.28 | 4.8 | 40.8 | ||||
| 12500 | 6.6 | 0.24 | 5.5 | 48.4 | ||||
| 16000 | 10.5 | 0.24 | 6.7 | 59.2 | ||||
| 20000 | 10.5 | 0.24 | 7.9 | 71.6 | ||||
| 25000 | 10.5 | 0.2 | 10.0 | 9.4 | 84.6 | |||
| 31500 | 10.5 | 0.2 | 11.1 | 100.8 | ||||
10kV oil-immersed three-phase double-winding unexcited voltage regulation distribution transformer energy efficiency class
Rated capacity (kVA) | Rated voltage and tapping range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | |||
|---|---|---|---|---|---|---|---|---|---|
| HV | Tap range (%) | LV | Dyn11/Yzn11 | Yyn0 | |||||
| 30 | 6,6.3,10,10.5 | ±2×2.5±5 | 0.4 | Dyn11Yzn11Yyn0 | 1.20 | 4.0 | 65 | 455 | 430 |
| 50 | 1.04 | 80 | 655 | 625 | |||||
| 63 | 0.96 | 90 | 785 | 745 | |||||
| 80 | 0.96 | 105 | 945 | 900 | |||||
| 100 | 0.88 | 120 | 1140 | 1080 | |||||
| 125 | 0.88 | 135 | 1360 | 1295 | |||||
| 160 | 0.80 | 160 | 1665 | 1585 | |||||
| 200 | 0.80 | 190 | 1970 | 1870 | |||||
| 250 | 0.72 | 230 | 2300 | 2195 | |||||
| 315 | 0.72 | 270 | 2760 | 2630 | |||||
| 400 | 0.64 | 330 | 3250 | 3095 | |||||
| 500 | 0.64 | 385 | 3900 | 3710 | |||||
| 630 | 0.48 | 4.5 | 460 | 4460 | |||||
| 800 | 0.48 | 560 | 5400 | ||||||
| 1000 | 0.48 | 665 | 7415 | ||||||
| 1250 | 0.40 | 780 | 8640 | ||||||
| 1600 | 0.40 | 940 | 10440 | ||||||
| 2000 | 0.32 | 5.0 | 1085 | 13180 | |||||
| 2500 | 0.32 | 1280 | 15270 | ||||||
10kV oil-immersed three-phase double-winding on-load regulating distribution transformer
Rated voltage (kVA) | Rated voltage and tapping range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | ||
| HV | Tap range (%) | LV | ||||||
| 200 | 6 6.3 10 10.5 | ±4×2.5 | 0.4 | Dyn11 Yyn0 | 0.8 | 4 | 0.31 | 2.9 |
| 250 | 0.72 | 0.35 | 3.42 | |||||
| 315 | 0.72 | 0.43 | 4.1 | |||||
| 400 | 0.64 | 0.51 | 4.95 | |||||
| 500 | 0.64 | 0.61 | 5.89 | |||||
| 630 | 0.48 | 4.5 | 0.77 | 7.26 | ||||
| 800 | 0.48 | 0.9 | 8.89 | |||||
| 1000 | 0.48 | 1.09 | 10.4 | |||||
| 1250 | 0.4 | 1.25 | 12.3 | |||||
| 1600 | 0.4 | 5 | 1.54 | 14.7 | ||||
| 2000 | 0.32 | 1.82 | 18.6 | |||||
| 2500 | 0.32 | 2.14 | 21.6 | |||||